EasyManua.ls Logo

Benning IT 110 - Trip-Out Time

Benning IT 110
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
5.3.7 Trip-out time (RCDt)
Trip-out time measurement is used to verify the effectiveness of the RCD. This is achieved by a
test simulating an appropriate fault condition. Trip-out times vary between standards and are listed
below.
Trip-out times according to EN 61008 / EN 61009:
½×I
N
*)
I
N
2×I
N
5×I
N
General (non-
delayed) RCDs
t
< 300 ms t
< 300 ms t
< 150 ms t
< 40 ms
Selective (time-
delayed) RCDs
t
< 500 ms
130 ms < t
<
500 ms
60 ms < t
<
200 ms
50 ms < t
<
150 ms
Trip-out times according to IEC 60364-4-41:
½×I
N
*)
I
N
2×I
N
5×I
N
General (non-
delayed) RCDs
t
< 999 ms t
< 999 ms t
< 150 ms t
< 40 ms
Selective (time-
delayed) RCDs
t
< 999 ms
130 ms < t
<
999 ms
60 ms < t
<
200 ms
50 ms < t
<
150 ms
Trip-out times according to BS 7671:
½×I
N
*)
I
N
2×I
N
5×I
N
General (non-
delayed) RCDs
t
< 1999 ms t
< 300 ms t
< 150 ms t
< 40 ms
Selective (time-
delayed) RCDs
t
< 1999 ms
130 ms < t
< 500
ms
60 ms < t
<
200 ms
50 ms < t
<
150 ms
*) Test current of ½×I
N
cannot cause trip-out of the RCDs.
How to perform trip-out time measurement:
Step 1 Select FI/ RCD TEST (RCD) with the function selector switch. Use the
/ . keys to se-
lect RCDt (trip-out time of the RCD). The following menu is displayed:
Fig. 5.17: Trip-out time measurement menu
Connect the test cable to the BENNING IT 110/ BENNING IT 120 B.
Step 2 Set the following measuring parameters:
- Nominal differential trip-out current
- Nominal differential trip-out current multiplier
- RCD type, and
- Test current starting polarity

Table of Contents

Related product manuals