EasyManua.ls Logo

Benning IT 110 - Loop Impedance and Prospective Short-Circuit Current (Zs; Ik); Loop Impedance (Loop Resistance, Zl)

Benning IT 110
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Save displayed results for documentation purposes. Refer to chapter 6.1 for further information on
setting functions and saving of measurement results (BENNING IT 120 only).
Note:
- The measurement of contact voltage in pre-test does not normally trip an RCD. However, the
triplimitmaybeexceededasaresultofleakagecurrentowingtothePEprotectiveconductor
or via a capacitive connection between L and PE conductors.
- The autotest sequence stops when the trip-out time is outside the allowed time period.
- Whensettingthefollowingparameters,theautomatictestingsequencewillbenishedalready
after having measured the time t4:
FI/RCD of type A, nominal fault current I
N
: 300 mA, 500 mA, 1000 mA
FI/RCD of type B, nominal fault current I
N
: 300 mA, 500 mA
- Whensettingthefollowingparameters,theautomatictestingsequencewillbenishedalready
after having measured the time t2:
FI/RCD of type B, nominal fault current I
N
: 1000 mA
5.4 Loop impedance and prospective short-circuit current (Zs/ Ik)
Two loop impedance measuring sub-functions are available:
- The Zl sub-function performs measurements in supply systems without RCDs.
- The Zs
rcd sub-function performs measurements in supply systems with RCDs installed (with
nominal differential trip-out current 10 mA)
5.4.1 Loop impedance (loop resistance, Zl)
The loop impedance is a complex AC impedance within the fault loop when a short-circuit to ex-
posed conductive parts occurs (conductive connection between phase conductor and protective
earth conductor). For measuring the loop impedance (loop resistance), the BENNING IT 110/
BENNING IT 120 B uses a 2.5 A test current.
The prospective short-circuit current (fault current) is calculated on the basis of the measured loop
impedance (loop resistance) as follows:
P PEL
n
PFC
R
scaling factorU
I
-
x
=
where
U
n
Voltage range
115 V 100 V U
L-PE
< 160 V
230 V 160 V U
L-PE
264 V
Becauseofdifferentdenitionsoftheprospectiveshort-circuitcurrent(faultcurrent)I
PFC
in diffe-
rent countries, the user can set the scaling factor in the Setup menu (see chapter 4.4.2).
PFC=Prospective Fault Current
How to perform the loop impedance measurement:
Step 1 Select Zs/Ik (L-PE) (loop impedance) with the function selector switch. Use the /
keys to select the Zl sub-function. The following menu is displayed:
Fig. 5.28: Loop impedance measurement menu

Table of Contents

Related product manuals