EasyManua.ls Logo

Benning IT 110 - Voltage; FI;RCD Testing; Line Resistance and Prospective Short-Circuit Current

Benning IT 110
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
75
Fault loop resistance
fault loop resistance both fault loops, R1 (L1-PE) and R2 (L2-PE)
prospective fault current I
SC1
and I
SC2
for both fault loops
Voltage, frequency symbols adapted to a power supply network with lower
voltage
Phase shift automatic recognition of three-phase mains
FI/RCD functions
contact voltage U
c
for both options, U1 (L1-PE) and U2 (L2-PE)
tripping time
maximum nominal differential current is limited to 1 Atripping current
automatic testing
Resistance to earth independent of the selected power supply network
PE conductor test key (TEST key) deactivated
12.3.1 Voltage
Figure 12.2: Example of voltage and frequency measurements
Displayed results for a single-phase system:
L1-L2 voltage between external conductors,
L1-PE voltage between external conductor 1 and protective conductor,
L2-PE voltage between external conductor 2 and protective conductor.
12.3.2 FI/RCD testing
The normal maximum FI/RCD testing current is 1 A RMS (peak current 1.4 A) and can only be
reached,ifthefaultloopresistanceisbelow1Ω.
Tests are carried out automatically for both combinations (L1-PE and L2-PE).
For each individual test result, the corresponding indication is shown.
Figure 12.3: FI/RCD contact voltage test
12.3.3 Line resistance and prospective short-circuit current
The measured resistance represents the phase-to-phase resistance (R
L1-L2
). The nominal voltage
for calculating I
PSC
is set to 110 V.
The nominal voltage range for measuring the line resistance is 90 V to 121 V. If the input voltage
is outside this range, this is displayed on the online voltage/ terminal monitor together with the
symbol.

Table of Contents

Related product manuals