EasyManua.ls Logo

Benning IT 110 - Testing Selective (Time-Delayed) Rcds; Contact Voltage

Benning IT 110
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
positive starting polarity
(0°)
negative starting polarity
(180°)
Fig. 5.13: Test current started with the positive or negative half-wave
For RCDs of type B, the fault current can be started with positive
or negative polarity.
During automatic testing (AUTO), the polarity is reversed automatically.
5.3.5 Testing selective (time-delayed) RCDs
SelectiveRCDsdemonstratedelayedresponsecharacteristics.Trip-outperformanceisinuenced
due to the pre-loading during measurement of contact voltage. In order to eliminate pre-loading a
time delay of 30 s is inserted before performing trip-out test.
5.3.6 Contact voltage (Uc)
LeakagecurrentowingtothePEterminalcausesavoltagedropacrossearthresistance,which
is called contact voltage. This voltage is present on all accessible parts connected to the PE termi-
nal and should be lower than the safety limit voltage.
The contact voltage is measured without tripping-out the RCD. R
L
is a fault loop resistance and is
calculated as follows:
Displayed contact voltage relates to the rated differential current of the RCD and is multiplied by a
safety factor. See the table 5.1 for detailed contact voltage calculation.
RCD type
Contact voltage Uc
proportional to
Nominal fault current I
∆N
AC G 1.05×I
∆N
Any
AC
S 2×1.05×I
∆N
A G 1.4×1.05×I
∆N
≥30mA
A
S 2×1.4×1.05×I
∆N
A G 2×1.05×I
∆N
< 30 mA
A
S 2×2×1.05×I
∆N
B G 2×1.05×I
∆N
Any
B
S 2×2×1.05×I
∆N
Table 5.1: Relationship between Uc and I
∆N
G = non-delayed fault current
S = time-delayed fault current (selective)
How to perform contact voltage measurement:
Step 1 Select FI/ RCD TEST (RCD) with the function selector switch. Use the / keys to se-
lect Uc (contact voltage).The following menu is displayed:

Table of Contents

Related product manuals