97
6 - PARAMETER DESCRIPTION
P31 Slow Speed Kick Time CFN 25
LED Display LCD Display
Range 0.1 – 10.0 seconds (Default 1.0)
Description The Slow Speed Kick Time parameter sets the length of time that the Slow Speed Kick current level (P30,
CFN 24) is applied to the motor at the beginning of slow speed operation. After the Slow Speed Kick Level is
set, the Slow Speed Kick Time should be adjusted so that the motor starts rotating when a slow speed
command is given.
If the motor initially accelerates too fast then reduce the Slow Speed Kick Level (P30 / CFN 24) and/or reduce
the Slow Speed Kick Time.
See Also Slow Speed Kick Level (P30 / CFN 24) parameter on page 96.
Theory of Operations section 7.6.2, Slow Speed Operation on page 157.
CFN: SSpd Kick T
25 1.0 sec