P40 Over/Under Voltage Trip Delay Time PFN 09
LED Display LCD Display
Range 0.1 – 90.0 seconds (Default 0.1)
Description The Voltage Trip Delay Time parameter sets the period of time that either an over voltage (P38 / PFN 07) or
under voltage (P39 / PFN 08) condition must exist before a fault occurs.
See Also Over Voltage Level (P38 / PFN 07) parameter on page 103.
Under Voltage Level (P39 / PFN 08) parameter on page 103.
Auto Reset Limit (P42 / PFN 11) parameter on page 104.
Controlled Fault Stop Enable (P43 / PFN 12) parameter on page 105.
P41 Auto Fault Reset Time PFN 10
LED Display LCD Display
Range Off, 1 – 900 seconds (Default Off)
Description The Auto Fault Reset Time parameter sets the time delay before the starter will automatically reset a fault.
For the list of faults that may be auto reset, refer to Appendix B - Fault Codes on page 196.
z NOTE: A start command needs to be initiated once the timer resets the fault.
See Also Auto Reset Limit (P42 / PFN 11) parameter on page 104.
Appendix B - Fault Codes on page 196.
P42 Auto Fault Reset Count Limit PFN 11
LED Display LCD Display
Range Off, 1 – 10 (Default Off)
Description The Auto Fault Reset Count Limit parameter sets the number of times that an auto reset may occur. Once the
Auto Reset Limit is reached, faults will no longer be automatically reset.
See Also Auto Fault Reset Time (P41 / PFN 10) parameter on page 104.
z NOTE: If the maximum reset count has been reached and the starter has locked out, only a user reset will
clear the reset counts.
z NOTE: If a few auto resets have been performed but the count has not reached the limit, the number of
accumulated resets will be cleared after 15 minutes if another fault does not occur.
z NOTE: The count can be always cleared by power cycling the starter.