6 - PARAMETER DESCRIPTION
P65 Keypad Stop Disable I/O 18
LED Display LCD Display
Range LED LCD Description
OFF Disabled Keypad Stop does not stop the starter
On Enabled Keypad Stop does stop the starter (Default)
Description If “Disabled”
When this parameter is set to "Disabled", the keypad [STOP] button is de-activated. This should be done with
caution, as the [STOP] key will not stop the starter.
The [STOP] key cannot be disabled if the keypad is selected as the control sources, .
If “Enabled”
When this parameter is set to "Enabled", the keypad [STOP] button is enabled and stops the starter regardless
of the selected control source (P4 / QST 04 or P5 / QST 05) selected as (keypad, terminal or serial).
See Also Local Source (P4 / QST 04) parameter on page 77.
Remote Source (P5 / QST 05) parameter on page 78.
P66 Auto Start Selection I/O 19
LED Display LCD Display
Range LED LCD Description
0 Disabled When Disabled, the Start input must always transition from low to high
for a start to occur. (Default)
1 Power When set to Power, a start will occur if the Start input is high while
control power is applied.
2 Fault When set to Fault, a start will occur if the Start input is high when a
fault is reset.
3 Power, Fault When set to Power and Fault, a start will occur if the Start input is
high while control power is applied, and a start will occur if the Start
input is high when a fault is reset.
Description The Auto Start parameter determines whether or not a transition from low to high is required on the Start input
for a start to occur after either a power up or a fault reset.
I/O: Keypad Stop
18 Enabled
I/O: Auto Start
19 Disabled