122
6 - PARAMETER DESCRIPTION
P71 Communication Byte Framing FUN 13
LED Display LCD Display
Range LED LCD
0 Even, 1 Stop (Default)
1 Odd, 1 Stop
2 None, 1 Stop
3 None, 2 Stop
Description The Communication Byte Framing parameter sets both the parity and number of stop bits.
See Also Communication Timeout (P68 / FUN 12) parameter on page 121.
Communication Baud Rate (P69 / FUN 11) parameter on page 121.
Communication Address (P70 / FUN 10) parameter on page 121.
P72 Energy Saver FUN 09
LED Display LCD Display
Range On – Off (Default Off)
Description The Energy Saver feature lowers the voltage applied to a lightly loaded motor. It continues to lower the
voltage until it finds the point where the current reaches its lowest stable level and then regulates the voltage
around this point. If the load on the motor increases, the starter immediately returns the output of the starter to
full voltage.
z NOTE: This function does not operate if a bypass contactor is used.
z NOTE: In general, Energy Saver can save approximately 1000 watts per 100 HP. Consult Benshaw for
further detail.
FUN: Com Parity
13 Even, 1 Stop
FUN: Energy Saver
09 Off