Chapter 5 – Parameter List
5-18
PARAM Description
LCD Keypad
Display Setting Range
Factory
Default
Adj.
During
Run Page
APP-59
Delay Time before
Stopping Aux Motor
Aux stop DT
0.0 - 999.9 sec 5.0 Yes 6-71
APP-60
Accel time when the
number of pump decreases
Pid AccTime
0 - 600.0 sec 2.0 Yes 6-71
APP-61
Decel time when the
number of pump increases
Pid DecTime
0 - 600.0 sec 2.0 Yes 6-71
APP-62 PID Bypass Selection
Regul Bypass
No
Yes
No No 6-71
APP-63
(Note 29)
Sleep Delay Time
Sleep Delay
0.0 - 9999 sec 60.0 Yes 6-72
APP-64 Sleep Frequency
Sleep Freq
0 - FUN-30 Hz 0.00 Yes 6-72
APP-65 Wake-Up Level
WakeUp level
0.0 - 100.0 % 35 .00 Yes 6-72
APP-66
(Note 28)
Auto Change Mode
Selection
AutoCh_Mode
0
1 (Aux)
2 (Main)
0 Yes 6-73
APP-67 Auto Change Time
AutoEx-intv
00:00 - 99:00 72:00:00 Yes 6-73
APP-68
Auto Change Frequency
AutoEx-Freq
FUN-32 -
FUN-30 Hz
20.0
Yes 6-73
APP-69
Inter-Lock Selection
Inter-lock
No
Yes
No Yes 6-75
APP-71
(Note 28)
Pressure difference for Aux
motor Start
Aux Stt Diff
0 - 100 %
2 Yes 6-76
APP-72
Pressure difference for Aux
motor Stopt
Aux Stp Diff
0 – 100% 2 Yes 6-76
APP-74
(Note 29)
PrePID Reference
Frequency
PrePID freq
0 - FUN-30 Hz 0 Yes
6-76
APP-75 PrePID Exit Level
PrePID Exit
0 - 100.0% 0 Yes
APP-76 PrePID Stop delay
PrePID dly
0 - 9999 600 Yes
APP-77 Pipe Broken
Pipe Broken
No, Yes No Yes
APP-78
(Note 28)
Stopping Order of Aux
Motors
First input – Last Output
F-In L-Out
Yes, No Yes No 6-77
APP-79
Stopping method of Aux
motors
All-Stop
Yes, No Yes No 6-77
APP-80
Ext PID Operation
Selection
Ext PI mode
No
Yes
No No 6-77
APP-81
(Note 33)
Ext PID Reference
Signal Selection
Ext Ref Sel
I
V1
Pulse
Keypad
Keypad No 6-77
APP-82
Ext PID
Reference Level
Ext Ref Perc
0 - 100.00 % 50.00 No 6-77