EasyManua.ls Logo

bonitron M3452 - Page 33

bonitron M3452
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User’s Manual
33
4.2.4.3.1.2. HEARTBEAT BIT 1
This bit changes states every 500ms. There is a rising edge
every 1 second, and can be used to indicate that the system
is still functional and communicating.
4.2.4.3.1.3. FAULT STATUS BIT 2
This indicates that there are no faults, and that the module is
operating properly.
4.2.4.3.1.4. ACTIVE BRAKING BIT 3
This indicates that the unit is actively braking, and follows the
red front panel indicator. (Section 4.2.1.3)
4.2.4.3.2. FAULT WORD WORD 1
This holds the current fault bits. The Fault states are listed in Section
4.2.5.
4.2.4.3.3. TEMPERATURE WORD 2
This indicates the temperature of the braking module heat sink in
degrees. This is a 16 bit unsigned integer that represents degrees
Fahrenheit. The resolution is to one degree, for example: 93 = 93°F.
The temperature feedback is valid when the heatsink temperature is
above 30°F. Below 30°F, the value will be zero. The value will also
be zero if there is an open thermocouple fault.
4.2.4.3.4. BUS VOLTAGE WORD 3
This indicates the present bus voltage in volts. This is a 16 bit
unsigned integer. The resolution is to one volt, for example, 675 =
675V.
4.2.4.3.5. DUTY CYCLE WORD 4
Word 4 indicates the present braking duty cycle of the module, with
0 representing fully off (0%) and 100 representing fully on (100%).
This is an 8 bit unsigned integer.
The duty cycle of the braking module is a 1 second average of the
high frequency pulse width during a braking cycle. This can give an
idea of the system loading during braking.
4.2.4.3.6. FAULT RECORDS WORDS 5 - 15
These words hold the last 10 fault states, oldest in the lowest
address.
The value stored is the fault state, as listed in Section 4.2.5.

Table of Contents

Other manuals for bonitron M3452

Related product manuals