02 Interior instant
03 Delay 1
04 Interior delay 1
05 Delay 1 Exit
06 Interior Delay 1 Exit
07 Delay 2
08 Interior Delay 2
09 Delay 2 Exit
10 Interior Delay 2 Exit
11 Follower
12 Interior Follower
13 24-Hour
14 Key AWAY Toggle
15 Key AWAY on/off
16 Key STAY Toggle
17 Key STAY on/off
18 24-Hour Panic
19 24-Hour Fire
20 24-Hour Fire with Verification*
21 Tamper
22 Bold Contact
23 External Fault
24 Technical Alarm
25 Reset
26 Instant Report
* Only possible for AMAX 4000 zone 1
00 – Not Used
If a zone is not used, program the zone type location to 0. An EOL resistor is not required if
this zone type is not used. This zone type never activates the sirens or the dialer.
01 – Instant
The instant zone type performs as described below:
1. Disarm:
– Zone normal - no alarm / no report
– Zone triggered - no alarm / no report
2. AWAY Arm:
– Zone normal - no alarm / no report
54
en | Settings AMAX panel
2015.05 | 06 | F.01U.309.277 Installation Manual Bosch Sicherheitssysteme GmbH