2. AWAY Arm: same as the delay zone AWAY arm status
3. STAY Arm:
This zone will be ignored and performed as disarm.
Refer to Keypad Indicators to see how the zone is displayed during exit time.
09 – Delay 2 Exit
The delay 2 exit zone type performs as described below:
1. DISARM: same as instant zone disarm status
2. AWAY Arm:
Zone normal - no alarm / no report
Zone triggered - entry time starts - no alarm / no report
Disarming during entry time - no alarm / no report
Zone triggered - during exit time - no alarm / no report / abbreviates remaining time
for exit to 5 seconds
Zone triggered - during entry time - no alarm / no report
Zone triggered - entry time is expired - alarm / report (report is delayed for 30
second, when system is disarmed before, no report)
3. STAY Arm: same as AWAY arm performance
First delay zone will start the entry time; all other delay zones will follow.
When system is disarmed and zone is not restored before, a zone restore report is
sent.
10 – Interior Delay 2 Exit
The Interior delay 2 exit zone type performs as described below:
1. Disarm: same as the instant zone disarm status
2. AWAY Arm: same as the delay exit zone AWAY arm status
3. STAY Arm:
This zone will be ignored and performed as disarm.
Refer to Keypad Indicators to see how the zone is displayed during exit time.
11 – Follower
The follower zone type performs as described below:
1. Disarm:
same as the instant zone disarm status
2. AWAY Arm:
Zone normal - no alarm / no report
Zone triggered – alarm / report
Zone triggered - during exit time - no alarm / no report
Zone triggered - during entry time - no alarm / no report
The remaining delay time is handed over from the delay zone to the follower zone.
The follower zone performance as the same as a delay zone.
If there are two or more zones programmed as delay zones and both are triggered,
the follower zone will follow the first triggered delay zone.
3. STAY Arm: same as the delay zone.
12 – Interior Follower
The interior follower zone type performs as described below:
1. Disarm: same as the instant zone disarm status
2. AWAY Arm: same as the follower zone AWAY arm status
AMAX panel
Settings | en 57
Bosch Sicherheitssysteme GmbH Installation Manual 2015.05 | 06 | F.01U.309.277