3. STAY Arm:
– This zone will be ignored and performed as disarm.
– Refer to Keypad Indicators to see how the zone is displayed during exit time.
05 – Delay 1 Exit
The delay 1 exit zone type performs as described below:
1. DISARM: same as instant zone disarm status
2. AWAY Arm:
– Zone normal - no alarm / no report
– Zone triggered - entry time starts - no alarm / no report
– Disarming during entry time - no alarm / no report
– Zone triggered - during exit time - no alarm / no report / abbreviates remaining time
for exit to 5 seconds
– Zone triggered - during entry time - no alarm / no report
– Zone triggered - entry time is expired - alarm / report (report is delayed for 30
second, when system is disarmed before, no report)
3. STAY Arm: same as AWAY arm performance
– First delay zone will start the entry time; all other delay zones will follow.
– When system is disarmed and zone is not restored before, a zone restore report is
sent.
06 – Interior Delay 1 Exit
The Interior delay 1 exit zone type performs as described below:
1. Disarm: same as the instant zone disarm status
2. AWAY Arm: same as the delay exit zone AWAY arm status
3. STAY Arm:
– This zone will be ignored and performed as disarm.
– Refer to Keypad Indicators to see how the zone is displayed during exit time.
07 – Delay 2
The delay 2 zone type performs as described below:
1. Disarm: same as instant zone disarm status
2. AWAY Arm:
– Zone normal - no alarm / no report
– Zone triggered - entry time starts - no alarm / no report
– Disarming during entry time - no alarm / no report
– Zone triggered - during exit time - no alarm / no report
– Zone triggered - during entry time - no alarm / no report
– Zone triggered - entry time is expired - alarm / report
– (report is delayed for a specified time (default: 30s; value range: 00-99), when
system is disarmed before, no report)
3. STAY Arm: same as AWAY arm performance.
– First delay zone will start the entry time; all other delay zones will follow.
– When system is disarmed and zone is not restored before, a zone restore report is
sent.
08 – Interior Delay 2
The interior delay 2 zone type performs as described below:
1. Disarm: same as the instant zone disarm status