Control Panels Appendix | en 167
Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996
B308 address number B9512G output numbers B8512G output numbers
52 521 – 528
53 531 – 538
54 541 – 548
55 551 – 558
56 561 – 568
57 571 – 578
58 581 – 588
59 591 – 598
22.1.4 D8128D address settings
The D8128D OctoPOPIT has two sets of DIP switches. Use the DIP switches on the top of the
unit (with the terminal strip along the left edge) to set the address for the OctoPOPIT. Use the
DIP switches at the bottom of the unit to enable or disable individual points connected to the
OctoPOPIT. The D82128D connects to the control panel through a B600.
ZONEX 1 D8128D address switches ZONEX 2
Output
number
1 2 3 4 5 Output
number
9 to 16 ON ON ON ON -- 129 to 136
17 to 24 ON ON ON OFF -- 137 to 144
25 to 32 ON ON OFF ON -- 145 to 152
33 to 40 ON ON OFF OFF -- 153 to 160
41 to 48 ON OFF ON ON -- 161 to 168
49 to 56 ON OFF ON OF -- 169 to 176
57 to 64 ON OFF OFF ON -- 177 to 184
65 to 72 ON OFF OFF OFF -- 185 to 192
73 to 80 OFF ON ON ON -- 193 to 200
81 to 88 OFF ON ON OFF -- 201 to 208
89 to 96 OFF ON OFF ON -- 209 to 216
97 to 104 OFF ON OFF OFF -- 217 to 224
105 to 112 OFF OFF ON ON -- 225 to 232
113 to 120 OFF OFF ON OFF -- 233 to 240
121 to 127 OFF OFF OFF ON -- 241 to 247
Notice!
For the D8128D OctoPOPITs assigned to Points 121 to 127, 241, and 247, set Point Input
Switch 8 to the OPEN position.
The B9512G uses Points 9 to 127 on ZONEX 1 and Points 129 to 247 on ZONEX 2.
B8512G uses only Points 9 to 99 on ZONEX 1.