18.1 Power supply side wiring
+
AUX PWR
ALARM TRIG
COM
SUPV IN
ALARM CKT
-
BAT 2+
BAT 1+
BAT 2-
BAT 1-
SUPV
CHGR+
CHGR-
VAUX+
6
7
11
10
12
13
9
5
8
USB POWER
STATUS
L
I
N
K
ETHERNETUSB
B
A
S
E
T
11
13 14
16
17
19
20
22
12
15
18
21
Quick Flash:
Low
BATTERY STATUS
Slow Flash:
Charging
Off: Normal
On:
Missing
Low 12.1 VDC
Load Shed 10.2 VDC
EARTH GROUND
COMMON
BATTERY (
-
)
+ AUX POWER
BATTERY ( + )
CLASS 2
16.5 VAC 40 VA 60 Hz
TRANSFORMER
10
9
8
7
6
5
4
3
2
1
OUTPUT
B (2)
OUTPUT
A (1)
OUTPUT
C (3)
Do not connect
to a receptacle
controlled by
a switch.
Point 5 Point 6
Point 3 Point 4
Point 1 Point 2 Point 7 Point 8
ON-BOARD POINTS
1 k End-of-line-Resistors Required (P/N 15093130-004),
WARNING!
Multi-Battery
installation requires
Model D122 or D122L
Dual Battery Harness.
Improper installation
can be a fire hazard
.
WARNING!
Incorrect wiring will
damage this
equipment.
Devices powered by
any output must be
supervised.
POWER SUPPL
The Power S
refer to the B
The system is intended
panel has been approv
RevPol.
Battery: Replace every 3 to
5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
WARNING!
To prevent risk of shock,
disconnect AC power and
communication lines before
servicing.
All exte
Require
Voltage Ranges: Open 3.7 - 5.0 VDC,
Owner I
be removed by
POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8
Callout á…³ Description Callout á…³ Description
1 á…³ D113 Supervision module, battery lead (if required
by local AHJ)
8 á…³ To control panel SDI2 wiring
2 á…³ Batteries 9 á…³ D192G Notification appliance module
3 á…³ D122/D122L Dual Battery Harness, as required 10 á…³ To OUTPUT A (1) or OUTPUT B (2)
4 ᅳ To supervision point 11 ᅳ 560 Ω, 2 W EOL resistor (P/N: 15-03130-005)
5 á…³Transformer 12 á…³ Listed audible signaling devices rated at 12.0 VDC
nominal (do not use vibrating type horns)
6 á…³ B520 Auxiliary Power Supply Module 13 á…³ To earth ground
7 á…³ To powered devices