122 en | Approved applications Control Panels
2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Prompt Possible Settings Recommendation
L## Reset Sensors Disable / Enable If Reset Sensor is set to Passcode
Protect, set this to Enable
L## Fire Test Disable / Enable If Fire Test is set to Passcode Protect,
set this to Enable
U### User Group 0 to 32 Program as 0
P## Ring Until Restored Yes / No May be required for Waterflow,
otherwise No
P## Cross Point Yes / No Set to No for Fire devices.
D# Fire Unlock Yes / No No
19.8 Required values to achieve 180s (ULC)/200s (UL) supervision
interval
Applicable for both IP and cellular communication.
Requirement Parameter
Supervision interval for IP and Cellular
communication is 200 seconds (UL)
Panel Wide Parameters > Enhanced Communications > Receiver
Supervision Time set to 200 seconds
Supervision interval for IP and Cellular
communication is 180 seconds (ULC)
Panel Wide Parameters > Enhanced Communications > Receiver
Supervision Time set to Custom, Poll Rate set to 89, ACK Wait
Time set to 15, and Retry Count set to 5
19.9 ULC
Conduct testing monthly, with the primary de-energized.