Address Switches
1 2 3 4 5 6
15 ON OFF OFF OFF ON
16 OFF OFF OFF OFF ON
22.2 Reporting and device number information
This section contains information to help you understand control panel reports.
22.2.1 Report format definitions
Notice!
Control panels using Modem4 send 4-digit Point and User data.
Panel event Modem4 code
D6500 mode
Modem4 code
Bosch SIA mode
Contact ID event Contact ID code
A point supervisory condition
occurred
Jspppp NriaBSpppp 24 hour Non-Burglary 1 150 aa ppp
A valid local RPS or Installer
Services Portal programming
tool (available in Europe,
Middle East, Africa, and
China) access occurred
RsF01 NLS Successful Download/
Access
1 412 00 000
A valid remote RPS or
Installer Services Portal
programming tool (available
in Europe, Middle East,
Africa, and China) access
callback occurred
RsssF NphhhRS Successful Download/
Access
1 412 00 000
A valid remote RPS or
Installer Services Portal
programming tool (available
in Europe, Middle East,
Africa, and China) access
occurred
RsssF NRS Successful Download/
Access
1 412 00 000
AC Fail - mains power supply Pssss NAT AC Loss 1 301 00 000
AC Restore - mains power
supply
Rsss0 NAR AC failure restore 3 301 00 000
Add Key Fob to a User
(Assign Card Event)
NsD30 NidiiiiDAiiii Local Only Local only
Alarm Aspppp NriaBApppp Burglary 1 130 aa ppp
Alarm Cross Point Aspppp NriaBMpppp Burglary 1 130 aa ppp
Alarm Exit Error Aspppp Nria/idiiiiEApppp Entry/Exit 1 134 aa ppp