20 en | System overview Control Panels
2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
A standard system user must have a passcode, a credential (token or card), and appropriate
command authority permissions assigned in the door to the assigned area of the keypad.
When enabled at a keypad, only the following Passcode Functions require access credentials
with passcode entry:
– Turn On/Turn Off
– Cycle Door (Grant Access)
– Cycle Output
– Auto Re-arm
Notice!
Plan ahead
If you plan to use Dual Authentication with access control, install a keypad close to the door
controller.
3.3.12 Recent closing
If a point with a point type set to 1, 2, or 3 goes into alarm within 2 minutes after the exit
delay expires, the control panel sends a Recent Closing Alarm. This feature is always enabled
and cannot be configured. The alarm with recent closing event creates new Modem4
messages that the central station might need to add to their automation software. For details
of central station data changes, refer to Events in the Modem4/ModemIIIa
2
Messages section of
the Appendix in the Conettix D6600/D6100i Computer Interface Manual (P/N: 4998122703).
3.4 Accessories
Accessory compatibility
The following table lists accessories that are compatible with the control panel. An X in a
column indicates the accessory is compatible with the standard.
Notice!
Where the fire alarm transmitter is sharing on-premise communications equipment, the
shared equipment must be UL Listed (ITE or fire protective signaling).
Model
number
Keypads
B915/B915I* X X X X X X X X X X X X
B920* X X X X X X X X X X X X
B921C*
1
X X X X X X X X
B925F* X X X X X X X X X X X X X
B926F* X X X
B930* X X X X X X X X X X X X
B942/B942W* X X X X X X X X X X X X