Control Panels Approved applications | en 121
Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996
Product feature/option Permitted in UL 864?
(Yes/No)
Possible settings Settings permitted in
UL 864
Sked## Wednesday Yes Yes / No Set to Yes
Sked## Thursday Yes Yes / No Set to Yes
Sked## Friday Yes Yes / No Set to Yes
Sked## Saturday Yes Yes / No Set to Yes
Sked## Xept On Holiday No Yes / No Set to No
Point Type (On-board, B208) Yes NEOL / DEOL /
2kEOL
Single / 2kEOL
For IP Communications to a D6600 Receiver
Enhanced Comm Yes Yes / No Set to Yes
Path # Network Address Yes IPV4 address or
hostname
Program a valid IPV4
address or hostname
Path # Receiver Supervision Time** Yes 200s, 300s, 1hr Select the Receiver
Supervision Time required
by your AHJ (200 seconds
or 300 seconds)
Path # Poll Rate Yes 0, 5 to 65535
seconds*
Program as necessary
Path # Ack Wait Yes 5 to 65535 seconds Program as necessary
Path # Retry Count Yes 1 to 255 Program as necessary
* Set the Path 1 Poll Rate to 65535 for 24 hr.
Use the following parameters for commercial fire alarm installations. Check with your local
Authority Having Jurisdiction.
UL 864 programming recommendations
Prompt Possible Settings Recommendation
Phone Line Fail Report Yes / No Yes
Phone Line Restoral Report Yes / No Yes
Fire Walk Start Report Yes / No Yes
Fire Walk End Report Yes / No Yes
Cancel Report Yes / No Yes
KP# Scope Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Do not program No Keypad
Function Lock (within the
Keypads section
Yes / No No
Reset Sensors Disable/Enable/Passcode Protect Enable
Fire Test Disable / Enable / Passcode Protect Enable