120 en | Approved applications Control Panels
2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Product feature/option Permitted in UL 864?
(Yes/No)
Possible settings Settings permitted in
UL 864
Bat Fail/Restoral Report Yes Yes / No Set to Yes
Area 1 Area On Required to send
system status reports
Yes / No Set to Yes
A# Delay Restoral Yes Yes / No Set to Yes
Restart Time Yes 5 to 55 seconds 5 seconds
Area # Fire Time Yes 1 to 90 min 5 min (check with AHJ)
Supervised (within the Keypads
section)
Yes Yes / No Set to Yes
Trouble Tone (within the Keypads
section
Yes Yes / No Set to Yes
Remote Program Disable / Enable -, E, or P Set to P
A# Fire Bell Yes 0 to 599 Program with a relay
A# Reset Sensors Yes 0 to 599 Program with a relay
U### Area # Auth Yes 0 to 13 Program an Authority Level
for the Fire Area
U### Passcode Yes 3-, 4-, 5-, or 6-digit
passcode
Must program at least one
passcode. Passcode must
have at least 4 digits.
P## Silent Bell No Yes / No Set to No
P## Invisible Point No Yes / No Set to No
P## Local While Disarmed No Yes / No Set to No
P## Local While Armed No Yes / No Set to No
P## Disable Restorals No Yes / No Set to No
P## Bypassable No Yes / No Set to No
P## Swinger Bypass No Yes / No Set to No
P## Resettable Yes Yes / No As required
Sked## Function Required Varies Sked Function Send Test
Report
Sked## Defer Test No Yes / No Set to No
Sked## Hourly Test (Report?) No Yes / No Set to No
Sked## Time Enter valid time 00:00 to 23:59 00:00 to 23:59
Sked## Date No mm/dd Set to No
Sked## Sunday Yes Yes / No Set to Yes
Sked## Monday Yes Yes / No Set to Yes
Sked## Tuesday Yes Yes / No Set to Yes