Control Panels Approved applications | en 119
Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996
Notice!
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, you must limit certain programming features or options to specific values.
UL 864 programming requirements
Product feature/option Permitted in UL 864?
(Yes/No)
Possible settings Settings permitted in
UL 864
Phone 1 through 4 Yes 24 characters Program a valid phone
number
Phone Supervision Yes 0 to 240 seconds 10 to 200 seconds
Alarm On Fail No Yes / No Set to No
Buzz On Fail Yes Yes / No Set to Yes
Two Phone Lines Yes Yes / No Set to Yes when using PSTN
communications.
Expand Test Report Yes Yes/No Set to Yes
Fire Reports Yes Yes / No Set to Yes
R# Fire Supervisory Missing Required Yes/No Set to Yes
Test Reports Yes Yes / No Set to Yes
AC Fail Report Yes Yes / No Set to Yes
AC Restoral Report Yes Yes / No Set to Yes
Battery Missing Report Yes Yes / No Set to Yes
Low Battery Report Yes Yes / No Set to Yes
Battery Restoral Report Yes Yes / No Set to Yes
R# Service Start Report Required Yes / No Set to Yes
R# Service End Report Required Yes / No Set to Yes
R# Fire Walk St Report Required Yes / No Set to Yes
R# Fire Walk End Report Required Yes / No Set to Yes
R# Walk Test St Report Required Yes / No Set to Yes
R# Walk Test End Report Required Yes / No Set to Yes
Ground Fault Detection Yes Enabled / Disabled Set to Enabled
AC Fail Time Yes 1:00 to 90:00 min Enter 1:00
AC Fail Display Yes 10 to 300 seconds 10 to 200 seconds
AC Tag Along Yes Yes / No Set to Yes
AC/Battery Buzz Yes Yes / No Set to Yes