General Information Regarding BUEP-E and BUEP19E
7--6
1070 072 196-101 (00.06) GB
Command Codes AST / PST
Parameter
Contents
Word
High Byte Low Byte
PW5 Command code AST Command code PST
Example 44
H
44
H
Data module Data module
The command code (Hex-code of the command) of the AST is specified in
the high byte of this parameter, and the command code of the PST is speci-
fied in its low byte.
Command Attribute AST
Parameter
Word
Contents
PW6 Command attribute AST
Example 17
H
Data module 23
Address AST High Part
Parameter
Word
Contents
PW7 Address AST high part
Example 10
H
ZS 2
In the PW7 parameter word, the block address of the module, to which the
AST command is referred, is specified.
Address AST Low Part
Parameter
Word
Contents
PW8 Address AST low part
Example 32
H
50 bytes
In the low part of the AST address, the byte address (offset) of the used com-
mand is specified.
Command Attribute PST
Parameter
Word
Contents
PW9 Command attribute PST
Example A
H
Data module 10