Modular Fire Panel Product Description | en 23
Bosch Sicherheitssysteme GmbH Product Information F.01U.028.089 | 5.4 | 2009.08
1.10 Hardware Accessories
1.10.1 UPS 2416 A Universal Power Supply 24 V/6 A
The UPS 2416 A is inserted into a power supply bracket and is ready for immediate operation.
It is protected against reverse polarity and surge. A green LED on the power supply unit
indicates its operational status. The temperature-dependent output voltage is monitored and
regulated by the BCM Battery Controller Module.
If 0 V is registered due to network failure or failure of the DC output voltage, the output FAULT
is triggered.
Technical specifications
WARNING!
The UPS 2416 A may only be used in the specially designated brackets and in a cover that
protects against fire (such as a panel housing).
Item Labeling Connector
1-2 ACL / ACN Mains supply
3 Protective ground
4-5 DC+ / DC- 26.76 V DC output plus / 0 V DC output minus
6 FAULT Output mains fault
7-8 RTH+ / RTH- Thermal sensor plus/minus
Input voltage range 100 V AC to 240 V AC
Input frequency 50 Hz to 60 Hz
Input current Max. 1.95 A
Efficiency > 85%
Back-up time > 16 ms at 115 V AC
Output voltage 26 V DC to 29 V DC
Maximum output current 6 A
Maximum power 160 W (permanent)
Cooling Ventilation without ventilator
Safety standards IEC 60950 / EN 60950
Permissible operating
temperature
-5 °C to 50 °C (23 °F to 122 °F)
Permissible storage
temperature
-20 °C to 60 °C (-4 °F to 140 °F)
Housing material and color Aluminum, anodized, black satin finish
12345678
LED
18