Modular Fire Panel Product Description | en 39
Bosch Sicherheitssysteme GmbH Product Information F.01U.028.089 | 5.4 | 2009.08
1.15.3 CZM 0004 A 4 Zone Conventional Module
The CZM 0004 A Conventional Module is used to connect certain conventional peripheries and
provides connections for four monitored conventional lines.
Technical specifications
NOTICE!
In line with EN 54-13, each conventional line must be terminated with EOL modules for the
operation of fire detection systems.
Labeling Connector
AUX1 + / AUX1 - 24 V DC auxiliary power supply zone 1
OUT1 - / OUT1 + Zone 1 output low / Zone 1 output high
IN1 - / IN1 + Zone 1 input low / Zone 1 input high
AUX2 + / AUX2 - 24 V DC auxiliary power supply zone 2
OUT2 - / OUT2 + Zone 2 output low / Zone 2 output high
IN2 - / IN2 + Class A zone 2 input low / Class A zone 2 input high
AUX3 + / AUX3 - 24 V DC auxiliary power supply zone 3
OUT3 - / OUT3 + Zone 3 output low / Zone 3 output high
IN3 - / IN3 + Class A zone 3 input low / Class A zone 3 input high
AUX4 + / AUX4 - 24 V DC auxiliary power supply zone 4
OUT4 - / OUT4 + Zone 4 output low / Zone 4 output high
IN4 - / IN4 + Class A zone 4 input low / Class A zone 4 input high
Operating and display elements 8 LEDs (4 x red, alarm / 4 x yellow, fault)
4 buttons (LED test)
Input voltage 20 V DC to 30 V DC / 5 V DC ± 5%
Maximum current consumption
- Standby mode (all four zones)
- In the event of an alarm (all four
zones)
65 mA
65 mA + 100 mA per zone (at 24 V DC)
Maximum output voltage 20 V DC ±5%
Maximum output current 100 mA ±10% per zone
Max. line resistance 2 x 25 Ohm per zone
Dimensions (H x W x D) Approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight without packaging Approx. 135 g (4.8 ounces)