Modular Fire Panel Product Description | en 41
Bosch Sicherheitssysteme GmbH Product Information F.01U.028.089 | 5.4 | 2009.08
1.15.5 FPE-5000-UGM Interface Module
The interface module is used to connect the FPA-5000 Module Fire Panel or an FPA-5000/
FMR-5000 network to a superordinate system such as the UGM 2020, FAT-2002/RE or FSM-
2000, and provides two two-way transmission links.
Technical specifications
Labeling Connector
SDI 1 + Transmission link 1 Data input +
SDI 1 - Data input -
SDO 1 + Data output +
SDO 1 - Data output -
SDI 2 + Transmission link 2 Data input +
SDI 2 - Data input -
SDO 2 + Data output +
SDO 2 - Data output -
Operating and display elements 4 two-color LEDs (green = transmitting/yellow =
malfunction)
1 button (LED test)
Input voltage 20 V DC to 30 V DC / 5 V DC ±5%
Maximum cable length 1000 m (3280 feet)
Maximum line resistance 70 Ohm
Baud rate 9600 bit/s at 1000 m (3280 ft) to 38,400 bit/s at 200 m
(656 ft)
Maximum current consumption
- Standby mode
- One transmission link active
- Both transmission links active
7mA (at 24V)
10 mA (at 24 V)
13 mA (at 24 V)
Dimensions (H x W x D) Approx. 110 x 90 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight Approx. 150 g (approx. 5.3 ounces)