62 en | Installation/Configuration Notes Modular Fire Panel
F.01U.028.089 | 5.4 | 2009.08 Product Information Bosch Sicherheitssysteme GmbH
3.6 System limiting values
For installation reasons, only 42 modules can be programmed when configuring a redundant
control panel. It is possible to have 46 modules per panel without redundancy if 1 housing
with the panel controller and 10 modules plus three housings with 12 modules each are
installed.
With redundancy, the redundant panel controller is installed in the fourth housing. In addition,
because the short panel rail (with two module slots) cannot be used, the fourth housing only
provides eight module slots (see also Section 3.11 Redundancy).
3.7 System limiting values of functional modules
General system limiting values Max. number
Control panels/remote keypads in the network
- Loop topology 32
- Bus topology, redundant 8
- Bus topology, non-redundant 8
Addresses
- Standalone control panel 4096
- In the network, total 32,512
- In the network, per control panel 2032
Detection points/detector groups
- Standalone control panel 4096
- In the network, total 32,512
- In the network, per control panel 2032
System limiting values per fire panel Max. number
Lists, e.g. bypass group 128
Total modules per panel 46
Printers 4
Alarm counters (external, internal, testing) 3
Entries in the event database 1000
Event entries in the event database from release 2.1 10,000
FSP-5000-RPS Programming Interfaces 1
Time control channels 20
Time control programs 19
Programming a specific day 365
User profiles 10
Access levels 4
NOTICE!
For systems conforming to EN 54-2, a redundant panel controller must be used when more
than 512 detectors are connected.
CTN Functional module Max. number
BCM-0000-B Battery Controller Module 8
CZM 0004 A CZM 0004 A 4 Zone Conventional Module 32