Modular Fire Panel Installation/Configuration Notes | en 63
Bosch Sicherheitssysteme GmbH Product Information F.01U.028.089 | 5.4 | 2009.08
3.8 Power Loss of All Components of the FPA-5000
LSN 0300 A LSN improved Module 300 mA 32
LSN 1500 A LSN improved Module 1500 mA 11
ANI 0016 A Annunciator Module 32
NZM 0002 A Notification Appliance Zone Module 8
RMH 0002 A RMH 0002 A Relay Module (for high voltage) 32
RML 0008 A Relay Module (for low voltage) 32
IOS 0232 A RS232 Communication Module 4
IOS 0020 A 20 mA Communication Module 4
FPE-5000-UGM Interface Module 4
IOP 0008 A Input/Output Module 32
ENO 0000 B Fire Service Interface Module 8
CTN Functional module Max. number
Component designation Power loss
MPC-xxxx-B 4.92 W
PRS 0002 A 0.18 W
PRD 0004 A 0.33 W
BCM-0000-B 0.96 W (controller + green LED lights up)
1.44 W (per AUX with 1.06 A load)
CZM 0004 A 1.65 W (for a line with 100 mA load)
3.36 W (for 4 lines with 100 mA load each)
LSN 0300 A 1.50 W (AUX with 490 mA load)
2.72 W (LSN)
LSN 1500 A 8.00 W (AUX)
14.70 W (LSN with 750 mA load)
NZM 0002 A 0.96 W
ANI 0016 A 0.62 W (all LEDs on)
RMH 0002 A 1.16 W
RML 0008 A 1.04 W (all relays activated)
IOS 0232 A 0.36 W
IOS 0020 A 0.36 W
FPE-5000-UGM 0.17 W
IOP 0008 A 0.24 W
ENO 0000 B 1.44 W (1 relay activated)
7.80 W (4 relays activated + key deposit heating active)
UPS 2416 A 28.00 W
FMR-5000 5.40 W