MAP 5000 Connections | en 41
Bosch Security Systems B.V. Installation manual 2019-09 | 25 | F.01U.168.332
3 Connections
!
Caution!
Wiring
Pinching of the wires is possible due to incorrectly hinged components.
Ensure that there is sufficient slack in the service wire loop to allow proper movement of
the hinged mounting plates.
Ensure that the wiring to and from components on the hinged bracket is properly secured
to the hinged mounting plates.
Ensure strain relief by means of the T cutouts.
Permitted LSN cable types
For all LSN MAP components and for all LSN connections, only shielded cables are permitted.
4 Ensure to connect the shield to the grounding studs.
!
Caution!
Wrong cable type
Using a wrong cable type can lead to malfunction of the system.
Use shielded cables only.
3.1 Connecting the data bus
To assist with cable connections, the terminal blocks on each system module are color-coded.
Terminal block color codes
Color Description
White Auxiliary power
Black AC / battery
Blue Inputs / tamper
Orange Outputs
Yellow DR2020 printer (ICP-MAP0007 only)
Brown LSN data (ICP-MAP0010 only)
Green Data bus
Connecting the data bus
1. Connect the system modules via the data bus.
2. Always use the main panel as the first device on the data bus. The 120 ohm end
terminator is already installed on every data bus.
3. Connect a 120 ohm end terminator to the last device on each data bus.