MAP 5000 Initial set-up and programming | en 63
Bosch Security Systems B.V. Installation manual 2019-09 | 25 | F.01U.168.332
4.6.2 Sirens and communicator in accordance with EN50131 grade 3
Notice!
Sirens must be in operation for at least 90 seconds and a maximum of 15 minutes, unless
local or national requirements demand a shorter duration.
The following variants are possible:
Variant A (ICP-MAP0007 DE module and ICP-COM-IF required)
– Two supervised sirens
Connections 10 / 11 and 12 / 13 on the ICP-MAP0007 DE module)
– One communicator (class 4)
Connections R1 – R7 on ICP-COM-IF
Variant B (ICP-COM-IF required)
– One self-powered siren
Outputs 10 / 11 or 13 / 14 on ICP-MAP5000 main panel
– One communicator class 4
Outputs R1 – R7 on ICP-COM-IF
Variant C (ICP-COM-IF required)
– One communicator class 4 (main communicator)
Outputs R1 – R7 on ICP-COM-IF
– One communicator class 3 (additional communicator)
Outputs R1 – R7 on ICP-COM-IF or other outputs on panel
Notice!
Both communicators may be connected to the same outputs.
Variant D (ICP-COM-IF required)
– One communicator class 5
Outputs R1 – R7 on ICP-COM-IF