MAP 5000 Appendices | en 75
Bosch Security Systems B.V. Installation manual 2019-09 | 25 | F.01U.168.332
2. Using the wizard, program one output with the behavior item Area Armed and a second
output with the behavior item Area Disarmed.
3. The signal must be time-limited. Enter a corresponding time (typically 10 sec. / maximum
30 seconds) for Activation Duration.
Securing access route against unauthorized entry in armed state, e.g. by installing a
blocking element
1. Connect a free output with the device LED.
2. Variant A: Blocking element is actively controlled CLOSED. Using the wizard, program an
output with the behavior item Area Armed
or
Variant B: Blocking element is actively controlled OPEN. Using the wizard, program an
output with the behavior item Area Disarmed.
3. The signal must be static; enter 00:00:00 for Activation Duration.
4. Refer to the manufacturer's connection instructions for further information.
8.2.4 Arming / disarming with entry / exit delay
Arming inside the secured area, e.g. with control center
1. Include a new area if not yet present.
2. Include a control center if not yet present.
3. Include the area in the scope of the control center: Local Area.
4. Program control center for arming with exit delay: Use Area Normal Delay Time.
5. The value for the entry / exit delay can be adapted if required: Area Manager > Area >
Timing and Delays:
normal entry delay (typically 45 sec. / at least 30 sec.)
normal exit delay (typically 60 sec.)
Programming entry / exit route
1. Program all points of the entry / exit route to the point type intrusion.
2. Select the type of exit point optionally for exit route points:
Exit point type Behavior
Initial follower
1
Point without prevention of arming readiness, e.g. PIR that has the
control center in the detection area. Important: point must be in
normal state after exit, otherwise an alarm will be tripped
Follower
1
Point that does not trip an alarm as long as the exit delay is
running. Only relevant for option MAP5000 Panel > Armed State At
Exit Delay Start
Exit Door point that must be mandatorily tripped once upon leaving the
area. The option MAP5000 Panel > Unvacated Premises must be
activated
Interrupt Door point that shortens the running exit delay to 10 sec.
(recommended)
Restart Point that restarts the exit delay; possible only once during the exit
Tab.8.3: Exit point types
1)
Not for EN 50131