37/57
Bosch Rexroth Canada ı 03.10.2011 ı Revision 5.4
Allow the system to run until the CALIBRATED catch pail is almost full.
Press the Enter button to stop the calibration process. The screen to the left will
appear.
Check the volume in the CALIBRATED catch pail and enter this value into the
controller.
Press the Enter button and using the Right/Left navigation arrows move the
cursor under the number to be changed.
Using the Up/Down navigational arrow, enter the volume of the material.
Once the proper volume has been entered, press the Enter button.
Using the Down navigational arrow, move the cursor to “ACCEPT VALUE”.
Press the Enter button again to confirm acceptance of the weight value, the
screen will return to the starting screen.
Note: The “pulses/ltr” number now reflects the value calculated from the results of
the calibration process.
Repeat this process for all liquids to be calibrated.