Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!20
6.3.6 Installing the condensate trap
High temperature applications:
z Fill the condensate trap (supplied with the boiler) with
water (fig. 13). Use mineral oil in case of high tempera-
ture systems and non-condensing applications.
z Connect the condensate trap (fig. 14, pos. 1) to the
condensate outlet. The condensate trap has a bayonet
connector, insert and turn ¼ rotation clockwise to click
into position.
z Connect the condensate trap hose (fig. 15, pos. 3) and
the rubber sleeve (fig. 15, pos. 2) to the condensate trap
(fig. 15, pos. 1).
Fig. 13 Filling the condensate trap with water
WARNING
Danger of fatal accident due to poisoning.
z If the condensate trap is not filled with water,
flue gas can escape and put people's lives at
risk.
Fig. 14 Installing the condensate trap
1
Fig. 15 Installing the condensate trap hose
1
2
3