Maintenance12
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!70
z Open the 2 clamps on the right and left at the bottom of
the condensate collector (fig. 92, pos. 1).
z Pull the condensate collector down (fig. 92, step 1) and
remove it by pulling it towards you (fig. 92, step 2).
z Check the condensate collector for damage and replace
it if required.
z Clean the condensate collector mechanically (using
compressed air or a soft brush) and rinse it with clean
water (fig. 93).
12.3.7 Clean the heat exchanger
z Clean the heat exchanger with compressed air or a soft
brush (fig. 94).
Fig. 92 Removing the condensate collector
1
2
1
1
Fig. 93 Cleaning the condensate collector
Fig. 94 Cleaning the heat exchanger
CAUTION
Incorrect handling can damage the boiler.
z Do not use metal brushes or similar hard
cleaning tools.
z Handle the glow ignitor with care, it is made
from fragile ceramic material.
z Cover the boiler interior using a blanket or a
cover to prevent dirt entering the boiler.
WARNING
Flue gas or condensate may leak if condensate
collector is installed incorrectly.