64
Maintenance and troubleshooting
Red
LED
Current
output
Transistor
output
Icon Message
displayed in the
Info menu
Possible cause Recommended action
ON 22 mA depending
on
thresholds
ERR
+
"S PT Missing" The connection to the
Pt1000 probe is lost.
The temperature
is displayed in the
Process level with
“+++++°C/°F”.
Check that the nut
between the sensor
holder and the elec-
tronic module is cor-
rectly screwed.
Send the device back
to Bürkert
ON 22 mA depending
on
thresholds
ERR
+
"S PT
Regulation"
The fluid temperature
is not being correctly
measured.
The process is stopped.
Switch the power
supply off then on
again.
if the error persists,
return the device to
Bürkert.
ON 22 mA depending
on
thresholds
ERR
+
"TR EE Fact
Read"
Parameter reading error. Switch the power
supply off then on
again.
if the error persists,
set the device back
to the default settings
(chpt. 9.11.4).
if the error persists,
return the device to
Bürkert.
"TR EE User
Read"
ON 22 mA depending
on
thresholds
ERR
+
"TR COM
Measure"
The acquisition/
conversion module of
the process values is
faulty.
The process is stopped.
Switch the power
supply off then on
again.
if the error persists,
return the device to
Bürkert.
ON 22 mA depending
on
thresholds
ERR
+
"TR EE
UserWrite"
Parameter saving error. Switch the power
supply off then on
again.
Save the settings
again.
if the error persists,
set the device back
to the default settings
(chpt. 9.11.4).
if the error persists,
return the device to
Bürkert.