9
Table 3A: Input / Output
Model
Input MBH
Gross Output
MBH
Turn-Down
Max
Min
ARN-1000
1000
47
945
21:1
ARP-1000
1000
100
945
10:1
ARN-1500
1500
60
1,416
25:1
ARP-1500
1500
150
1,416
10:1
ARN-2000
2000
80
1,886
25:1
ARP-2000
2000
200
1,886
10:1
ARN-2500
2500
100
2,355
25:1
ARP-2500
2500
250
2,355
10:1
ARN-3000
3000
120
2,841
25:1
ARP-3000
3000
300
2,841
10:1
ARN-3500
3500
140
3,325
25:1
ARP-3500
3500
350
3,325
10:1
ARN-4000
4000
160
3,748
25:1
ARP-4000
4000
400
3,748
10:1
Table 3B: Water Content
Model
Volume (Gallon)
AR(N,P)-1000
55
AR(N,P)-1500
68
AR(N,P)-2000
96
AR(N,P)-2500
96
AR(N,P)-3000
107
AR(N,P)-3500
120
AR(N,P)-4000
120
Table 3C: Minimum Flow Rate at Maximum Fire Rate
Model
Flow (GPM)
AR(N,P)-1000
23.6
AR(N,P)-1500
35.4
AR(N,P)-2000
47.1
AR(N,P)-2500
58.8
AR(N,P)-3000
71.0
AR(N,P)-3500
83.1
AR(N,P)-4000
93.6
Based on maximum temperature rise of 80°F
Table 3D: Absolute Minimum Flow Rate
Model
Flow (GPM)
AR(N,P)-1000
7.9
AR(N,P)-1500
11.8
AR(N,P)-2000
15.7
AR(N,P)-2500
19.6
AR(N,P)-3000
23.7
AR(N,P)-3500
27.7
AR(N,P)-4000
31.2