EasyManua.ls Logo

Camus Hydronics Avenger Series - Location of a Sidewall Air Inlet Terminal; Length of Air Inlet Pipe

Camus Hydronics Avenger Series
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Room Air, Vent Terminal Clearances
Canadian Installations
1
US Installations
2
A
Clearance above grade, veranda, porch, deck, or
balcony
12” (30 cm)
12 in (30 cm)
B
Clearance to window or door that may be opened
36” (91 cm)
4’ (1.2 m) below or to side of
opening; 1’ (30 cm) above
opening
C
Clearance to window or door that may be opened
*
*
D
Clearance to permanently closed window
*
*
E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
*
*
G
Clearance to inside corner
*
*
H
Clearance to each side of center line extended above
meter/ regulator assembly
36” (91 cm) within a height of
15’ (4.5 m) above the meter/
regulator assembly
*
I
Clearance to service regulator vent outlet
36” (91 cm)
*
J
Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance
36” (91 cm)
4’ (1.2 m) below or to side of
opening; 1’ (30
cm) above
opening
K
Clearance to a mechanical air supply inlet
6’ (1.83 m)
3’ (91 cm) above if within 10’
(3 m) horizontally
L
Clearance above paved sidewalk or paved driveway
located on public property
7’ (2.13 m)
α
*
M
Clearance under veranda, porch deck, or balcony
12” (30 cm)
β
*
1
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2
In accordance with ANSI Z223.1/ NFPA 54 National Fuel Gas Code
α
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and
serves both dwellings
β
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/ NFPA 54 or CSA-B149.1. Clearance in accordance with local installation codes
and the requirements of the gas supplier
2.4.3 LOCATION OF A SIDEWALL AIR INLET TERMINAL
The termination point of the sidewall air inlet must be installed a minimum of 3 feet above normal levels of snow accumulation.
Models 1000 1500: The point of termination for the sidewall combustion air inlet terminal MUST be located a minimum 18
inches (45 cm) below the point of flue gas termination (vent cap).
Models 2000 4000: The point of termination for the sidewall combustion air inlet terminal MUST be located a minimum of 36”
(90 cm) below the point of flue gas termination (vent cap).
The sidewall vent and air termination must be purchased with the boiler to ensure reliable boiler operation.
2.4.4 LENGTH OF AIR INLET PIPE
The maximum total length of the sidewall or vertical roof top combustion air inlet pipe as installed from the appliance to the air inlet
terminal must not exceed 100 equivalent feet (30.5 m) in length. Subtract 7 (2.13 m) to 19 feet (5.8 m) of equivalent length depending on
centerline radius for each 90° elbow installed in the air inlet pipe system. Pressure drop in 45° elbow will be half as much.
Vent
Models 1000-1500:
18” (45 cm) Minimum
Models 2000-4000:
36” (90 cm) Minimum
Air
Intake
36"
Normal Snow Level

Table of Contents

Related product manuals