6.2.3 STATISTICS CONFIGURATION
Menu Group
Selection
Sub-Menu
Group Selection
Parameter Selection Description
Statistics
Configuration
Boiler pump cycles
Displays the number of cycles the boiler pump has
been activated
Burner cycles
Displays the number of cycles the burner has been
activated
Burner run time Displays burner run time in hours
CH pump cycles
Displays the number of cycles the CH pump has been
activated
DHW pump cycles
Displays the number of cycles the DHW pump has
been activated
6.2.4 BURNER CONTROL TIMING AND RATES
Figure 30: Burner Control Timing and Rates
Menu Group
Selection
Sub-Menu
Group Selection
Parameter Selection Description
Burner Control
Timing and
Rates
Prepurge rate 3000 RPM Prepurge fan speed (Default: AR1000-AR4000: 60.0%)
Prepurge time 25 sec..5 mins Prepurge time (Default: 25 sec)
Run Stabilization
Time
10 sec Main flame establishing period
Postpurge rate 3000 RPM Postpurge fan speed (Default: AR1000-AR4000: 60.0%)
Postpurge time 25 sec..5 mins Postpurge time (Default 25 sec)
6.2.5 BURNER CONTROL IGNITION
Menu Group Selection
Sub-Menu
Group Selection
Parameter Selection Description
Burner Control Ignition
Light-off rate AR1000-AR4000: Refer to factory test sticker Ignition Fan Speed