EasyManua.ls Logo

Camus Hydronics Avenger Series - Configure Menu; System Identification & Access; Pump Configuration

Camus Hydronics Avenger Series
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
6.2 CONFIGURE MENU
Figure 29: Configure Menu
6.2.1 SYSTEM IDENTIFICATION & ACCESS
Menu Group Selection
Parameter
Description
System Identification & Access
Product Type
Commercial Hydronic Boiler
OS number
Part Number of SOLA Controller
Software Version
Software Version
Date Code:
Release Date of Software
Boiler Name
Avenger Model Number
6.2.2 PUMP CONFIGURATION
Menu Group
Selection
Sub-Menu
Group Selection
Parameter Selection Description
Pump
Configuration
Central Heat
Pump
Pump Control
Auto
Assigns the method for SOLA to
control a Central Heating pump
(Default: Auto, Pump is activated
whenever a call for heat is
present)
ON
ON: Pump is constantly powered
Pump Output
Pump B
Specify pump contact
Over run time
1..5 min
Post pump time (Default: 1 min)
Use for local (Stand-alone)
demands
Use for Lead Lag Master
demands
Boiler Pump
Pump Control
Auto
Refer to above (Default)
ON
Refer to above
Pump Output
Pump A
Specify pump contact
Over run time
1..5 min
Post pump time (Default: 1 min)
Use for local (Stand-alone)
demands
Use for Lead Lag Master
demands
Pump
Configuration
DHW Pump
Pump Control
Auto
Refer to above (Default)
ON
ON: Pump is constantly powered
Pump Output
Pump B
Specify pump contact
Over run time
1..5 min
Post pump time (Default: 1 min)