6.2 CONFIGURE MENU
Figure 29: Configure Menu
6.2.1 SYSTEM IDENTIFICATION & ACCESS
System Identification & Access
Commercial Hydronic Boiler
Part Number of SOLA Controller
6.2.2 PUMP CONFIGURATION
Parameter Selection Description
Pump
Configuration
Central Heat
Pump
Pump Control
Auto
Assigns the method for SOLA to
control a Central Heating pump
(Default: Auto, Pump is activated
whenever a call for heat is
ON: Pump is constantly powered
Post pump time (Default: 1 min)
Use for local (Stand-alone)
demands
Use for Lead Lag Master
demands
Boiler Pump
Pump Control
Post pump time (Default: 1 min)
Use for local (Stand-alone)
demands
Use for Lead Lag Master
demands
Pump
Configuration
DHW Pump
Pump Control
ON: Pump is constantly powered
Post pump time (Default: 1 min)