36
Table 12: Alert Codes
#
Description
29
Burner switch turned OFF
30
Burner switch turned ON
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
81
Delta-T limit exceeded (70
°
F)
110
Ignition failure occurred
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to sensor failure
229
Lead lag slave communication timeout.
275-281
LCI off, safety circuit is open
283
Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of Ignition period
292
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-310
+
Interlock Off, safety circuit is open
324, 374-379
Hardware flame bias. Flame sensor wire needs to be re-routed.
352
+
Stack sensor fault
355
+
Outlet sensor fault
357
+
DHW sensor fault
359
+
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
614
Lead boiler was rotated due to measured run time
* If an internal hardware fault is detected, contact Camus Technical Support for troubleshooting procedure.
+
The alarm LED and alarm contacts closed and remain closed until the ‘RESET’ button is pressed.