EasyManua.ls Logo

Camus Hydronics Avenger Series - Page 68

Camus Hydronics Avenger Series
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
Table 17: Alert Codes
#
Description
29
Burner switch turned OFF
30
Burner switch turned ON
50
Modulation Fault
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
81
Delta-T limit exceeded (70ºF)
110
Ignition failure occurred
123
Modulation rate was Limited due to outlet limit
124
Modulation rate was Limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to sensor failure
229
Lead lag slave communication timeout.
275-281
LCI off, safety circuit is open
283
Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of Ignition period
292
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-310
+
Interlock Off, safety circuit is open
324, 374-379
Hardware flame bias. Flame sensor wire needs to be re-routed.
352
+
Stack sensor fault
355
+
Outlet sensor fault
357
+
DHW sensor fault
359
+
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
614
Lead boiler was rotated due to measured run time
+
The alarm LED and alarm contacts are closed and will remain closed until the ‘RESET’ button is pressed.
Alert 291: Abnormal Recycle: Flame was not ON at the end of ignition
Alert 294: Abnormal Recycle: Flame was lost during Run
Alert 324: Abnormal Recycle: Hardware flame bias
Alert 377: Abnormal Recycle: Hardware flame bias delta
These errors occur when a flame signal is not detected by the UV Scanner. A minimum signal of 0.8Vdc must be detected by the UV
Scanner to prove the flame.
For High-End Valve, staging relay switch over is factory set and normally does not require field adjustment.
Check UV Scanner wire
Move UV Scanner wire
away from harness
bundle
Check hot surface igniter
for minimum 3.0A
reading
Replace igniter
Check UV Scanner
viewing window for
carbon deposit
Clean and/or replace
Within harness bundle
No
Yes
Separated from
harness bundle
Yes

Table of Contents

Related product manuals