6. ELECTRICAL CONNECTIONS
WARNING: electric shock hazard. Before making the electrical
connections, the appliance must be disconnected from the mains power
supply and must be prevented from being powered on. Electrical
disconnection must be veried by measurement.
NOTICE: correct wiring of the ultrasound humidier is the responsibility of the
installer of the nal appliance manufacturer, as required by IEC EN 60335-1.
6.1 Electrical installation
Main board
Fig. 6.a
Key
A Power supply input to the board from the transformer 24V
B Supply and controller cable driver;
Power supply input to the board from the transformer 50V
C valve power cables (L drain / R ll)
D conguration dipswitch
E TAM (current transformer) input for measuring current on external fan
F (not use for this application)
G TH temperture and humidity probe connection (IIC digital serial, part
no.: HYHU000000) optional.
M14 remote ON/OFF (M14.1-M14.2)
M11 RS4845 serial (M11)
M15 - N.O. alarm relay (M15.1-M15.2)
- 30 Vdc output (24 Vac rectied , max. 3W) (M15.3-M15.4)
N auxiliary card connection
Electrical connections
GND
GND
+21V
F
Level ow
switch
Fan
+ GND
Piezoelectric
transducer
Pool
Driver
D
Driver
Control
board
Drain
valve
Fill
valve
FAN
HIGH LEV.
LOW LEV.
230 Vac
50 Vac
L
N
24 Vac
L N
L N
24Vac
Drivers
C A
B
1 2
3 4
5 6
7 8
{
50Vac
Fill
Drain
Fig. 6.b
6.2 Internal electrical connections
1. Connect the wires from connector C to the ll and drain valves;
2. Connect the power and control cables to the driver card(s) positioned
under the tank, in accordance with the wiring diagram and the
screen printing on the cables (photo).
48(1)-[6]
48(2)-[7]
48(1)+[2]
48(2)+[3]
Fig. 6.c
6.3 Power supply
• Check that the power supply voltage of the appliance corresponds to
the value indicated on the rating plate.
• Connect the 50 Vac transformer output to terminals 1 and 5 on
connector B;
• Connect the 24 Vac transformer output to the terminals on connector A;
• Connect the transformer input cable to the mains. The humidier
power line must be tted with a disconnect switch.
NOTICE: to avoid unwanted interference, the power cables should be
kept separate from the probe signal cables.
Once the electrical and water connections have been completed, the
humidier is ready for operation.