“Ultrasound for fancoil” +0300059IE - rel. 1.7 - 24.10.2022
15.1 Ultrasound humidier models for fan coils and electrical specications
The table below summarises the electrical data (power supply voltages) of the various models, as well as their functional characteristics. Note that some
models can be powered at dierent voltages, obviously with dierent current and humidity production values.
power supply
model humidity production
(2; 4)
(kg/h) power
(2)
(W) code voltage
(1)
(V - type) current
(2)
(A) cable
(3)
(mm
2
)
UU01FD 0,5 60 D 230-1~ 0,75 1,5
UU01F1 0,5 60 1 115 - 1~ 0,6 1,5
UU01GD 1 110 D 230 - 1~ 1,5 1,5
UU01G1 1 110 1 115 - 1~ 1,2 1,5
Tab. 15.a
(1) tolerance allowed on rated mains voltage: -15%, +10%;
(2) tolerance on rated values: +5%, -10% (EN 60335-1);
(3) recommended values, referring to PVC or rubber cable in a closed conduit, 20 m (65.6 ft) long; compliance with standards in force is always required;
(4) max instant rated water vapour production: average water vapour production may depend on external factors, such as: room temperature, water quality, water vapour distribution
system.
NOTICE: to avoid interference, keep power cables separate from probe cables.
15.2 Technical specications
Technical specications UU models
UU01*
humidity outlet
connection dia. mm 40 (ensure an outlet area of 1100 mm2, e.g. 22 x 8 mm holes)
supply water
connection G 1/8” F
temperature limits °C (°F) 1...40 (33.8....104)
pressure limits (MPa) 0,1...0,6 (1...6 bar)
specic conductivity at 20°C 3...50 μS/cm
total hardness 0...25 mg/l CaCO3
temporary hardness 0...15 mg/l CaCO3
total quantity of dissolved solids (cR) depending on specic conductivity
(1)
dry residue at 180°C depending on specic conductivity
(1)
iron + manganese G 1/8” F
chlorides 1...40 (33.8....104)
silicon dioxide 0,1...0,6 (1...6 bar)
chlorine ions 0...50 μS/cm
calcium sulphate 0...25 mg/l CaCO3
instant ow-rate (l/min) 0...15 mg/l CaCO3
drain water
connection dia. mm (“) 10 mm
instant ow-rate (l/min) 7
environmental conditions
ambient operating temperature °C (°F) 1...45 (33.8...113)
ambient operating humidity (% rH) 10...80
storage temperature °C (°F) -10...60 (14...140)
storage humidity (% rH) 5 to 95 (41 to 203)
index of protection IP00
electronic controller
auxiliary voltage/frequency (V- Hz) 24 V / 50-60 Hz
maximum auxiliary power (VA) 3
control signal inputs (general features) can be selected for the following signals: 0 to 10 Vdc, 2 to 10 Vdc, 0 to 20 mA, 4 to 20 mA,
input impedance: 20 kΩ with signals: 0 to 10 Vdc, 2 to 10 Vdc
100 Ω with signals: 0 to 20 mA, 4 to 20 mA
alarm relay outputs (general features) 24 V (max 3 W)
remote enabling signal input (general features) voltage-free contact; max. resistance 100 Ω; Vmax= 5 Vdc; Imax= 5 mA
power
instant water vapour production
(2)
kg/h (lb/h) see table above
power consumption at rated voltage (W) see table above
Tab. 15.b
(1)
= in general C
R
≅ 0,65 * σ
R,20 °C
; R
180
≅0,93 * σ
R, 20 °C
(2 )
= average water vapour production is aected by factors such as: room temperature, water quality, water vapour distribution system
15. GENERAL FEATURES AND MODELS