Installing the i-Vu® Open Link
i-Vu Open Link Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide All rights reserved
16
For the Open controllers connected to the i-Vu® Open Link
BACnet MS/TP Device Instance Number = 161xxyy
BACnet ARC156 Device Instance Number = 163xxyy
BACnet MS/TP Device Instance Name = device161xxyy
BACnet ARC156 Device Instance Name = device163xxyy
BACnet MS/TP or ARC156 MAC Address = yy
BACnet MS/TP Network Number = 161xx (learned from the router, defaults to 16101 if no i-Vu® Open Link is
operating)
If the BACnet automatic settings need to be changed, launch the
Router Configuration utility using a terminal
program. See To assign a custom IP address for instructions on connecting to and using a terminal program.
To change the BACnet settings:
1 Enter the BACnet selection# from the menu. Type the new setting and click Enter. The new setting will appear
on the Router Configuration screen.
2 Cycle power to the router for the new settings to take effect.
NOTE If the BACnet MS/TP or ARC156 network number of the router is assigned and not auto-generated,
and the Open controllers connected to that router are set such that their BACnet settings are auto-generated,
then the Open controller BACnet settings will be auto-generated based on the assigned MS/TP network
number in the router:
Example A router's BACnet MS/TP or ARC156 network has been assigned to 200.
If the connected Open controllers are using autogenerate, then their settings will be:
BACnet MS/TP Network Number = 200
BACnet Device Instance Number = 200yy
BACnet Device Instance Name = device200yy
BACnet MS/TP MAC Address = yy