Configuring i-Vu® Open Link Driver Properties
   
 
i-Vu Open Link  Carrier Proprietary and Confidential  CARRIER CORPORATION ©2017  
Installation and Start-up Guide    All rights reserved 
  21 
 
Time Synch Sensitivity 
(seconds) 
When the controller receives a time sync request, if the difference between the 
controller's time and the time sync's time is greater than this field's value, the 
controller's time is immediately changed. If the difference is less than this field's 
value, the controller's time is slowly adjusted until the time is correct.
 
Under normal circumstances, COV Throttling should be enabled to prevent 
excessive network traffic if an object's COV Increment is set too low. See 
EXCEPTION below. 
When enabled, if an object generates excessive COV broadcasts (5 updates in 3 
seconds), the driver automatically throttles the broadcasts to 1 per second. Also, 
if the object's value updates excessively for 30 seconds, an alarm is sent to the i-
Vu® or Field Assistant application listing all objects that are updating 
excessively. A Return-to-normal alarm is sent only after all objects have stopped 
updating excessively. 
EXCEPTION:  In rare circumstances, such as process control, a subscribing object 
may require COV updates more frequently than once per second. For these 
situations, clear this checkbox, but make sure that your network can support the 
increased traffic. You will also need to disable the Excessive COV alarms under 
the driver's Common Alarms.  
 
 
 
 
Device
 
On the Driver
 > Device 
page, you can change the following properties: 
•  BACnet device object properties for the i-Vu® Open Link 
•  i-Vu® Open Link communication 
 
NOTE The three APDU fields refer to all networks over which the i-Vu® Open 
Max Masters and Max Info 
Frames 
Max Masters - defines the highest MS/TP Master MAC address on the MS/TP 
network.  
For example, if there are 3 master nodes on an MS/TP network, and their MAC 
addresses are 1, 8, and 16, then Max Masters would be set to 16 (since this is 
the highest MS/TP MAC address on the network).  
This property optimizes MS/TP network communications by preventing token 
passes and “poll for master” requests to non-existent Master nodes.  
In the above example, MAC address 16 knows to pass the token back to MAC 
address 1, instead of counting up to MAC address 127. Each MS/TP master 
node on the network must have their Max Masters set to this same value. The 
default is 127. 
Max Info Frames - defines the maximum number of responses that will be sent 
when the i-Vu® Open Link receives the token. Any positive integer is a valid 
number. The default is 10 and should be ideal for the majority of applications. In 
cases where the i-Vu® Open Link is the target of many requests, this number 
could be increased as high as 100 or 200.