EasyManua.ls Logo

Carrier i-Vu Open Link - BACnet Router Properties; BACnet Firewall Configuration; Alarm Store and Forward

Carrier i-Vu Open Link
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring i-Vu® Open Link Driver Properties
i-Vu Open Link Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide All rights reserved
24
BACnet router properties
On the BACnet router properties page, you can change the following properties:
BACnet routing settings
Color and prime variable caching settings
BACnet Router Options
Ignore all Reject-Message-to-
Network, Reason=1
messages
Clear to delete and redownload a router if a network's router indicates that the
network is no longer present (reason=1).
Select to continue routing messages to a network even if its router indicates that
the network is no longer present.
Color/Prime Variable
Caching
Disable Color Cache
Clear (enable) to improve responsiveness in retrieving colors.
Select (disable):
To reduce network traffic to third
-party (non-color
-supporting) devices
If using the i-Vu®
Open Link on the controller network, but not as a router
NOTE
Selecting this checkbox also disables dead controller alarms.
Dead Module Timeout
After this period (minutes:seconds) of non
-response from an Open controller, the
router sends an alarm to the server.
BACnet firewall
Requires v6
-02 or later driver
If this IP controller is accessible from the Internet, you can increase security by enabling its BACnet firewall. When
enabled, this feature prevents the controller from receiving BACnet messages from unidentified sources and
allows communication only with IP addresses that you define. These can be all private IP addresses and/or a list
of IP addresses. Follow the instructions in the i-Vu® or Field Assistant interface to set up the BACnet firewall.
Alarm Store/Forward
On the
Alarm Store and Forward page, you can change alarm delivery settings for the i-Vu® Open Link used to
store and forward alarms from a remote dial
-up site.