(0.01 ~ 99.99) Hz/s
(0.0 ~ 6500.0)s
(0.0 ~ 6500.0)s
(0.5 ~ 16.0)kHz
0 : no
1 : yes
–
0: invalid
1: Valid throughout
2: Only invalid when decelerating
0: invalid operation
1: Clear fault record information ( including fault
information and accumulated power)
2: Restore factory parameters (except motor
parameters)
3: Custom parameters restore factory defaults
(except motor parameters)
4: All parameters are restored to factory values
5: Backup parameters
6: Use backup parameters
7: Save backup parameters
Note: Only when the backup parameters are used,
the backup parameters can be saved; otherwise,
when the power is turned on after power off, except
for the modified parameters, other parameters are
still the original parameter values.
Ones place: After the panel UP/DN modifies the
frequency
0: The frequency is not stored when power off
1: frequency power-down storage
Tens digit: After the panel UP/DN modifies the
frequency
0: stop frequency keep
1: Shutdown frequency restores to initial value
Hundreds place: After the terminal UP/DN modifies
the frequency
0: The frequency is not stored when power off
1: frequency power-down storage
Thousands digit: After the terminal UP/DN modifies
the frequency
0: stop frequency keep
1: Shutdown frequency restores to initial value
(0 ~ 440 )V
1.00 Hz/s
Model
confirmed
Model
confirmed
Model
confirmed
1
–
2
0
0x0000
by
frequency
converter
series
decision
F0.12
F0.14
F0.15
F0.16
F0.17
F0.18
F0.19
F0.20
F0.13
F0.11
Panel UP/DN adjustment rate
Acceleration time 1
Deceleration time 1
carrier frequency
Carrier frequency automatic
adjustment
reserve
Automatic voltage regulation
(AVR) function
parameter initialization
UP/DN adjustment control
output voltage
F0.09 ~ F0.08
F0.09 ~ F0.07
0.00Hz ~ F0.08
0.00Hz ~ F0.07
50.00Hz
50.00Hz
50.00Hz
0.00Hz
50.00Hz
F0.05
F0.08
F0.09
F0.10
0 : run in the default direction
1 : run in the opposite direction
2 : Reverse operation prohibited
F0.06
0
F0.07
digital setting
frequency cap
Operating frequency lower limit
Basic operating frequency
Running direction setting
output frequency
F0.08 ~ 600.00Hz
function
code
name
Parameter Description
Defaults
Change
089
NVF2G-S Series Inverter User's Guide