61
Table 3.5.1 · MODBUS register map - conguraon registers (connued)
REGISTER
NUMBER
NAME DESCRIPTION
OPTIONS and
REGISTER VALUE
DEFAULT
DATA
TYPE
READ
or
WRITE
66 - 69 UNUSED Unused N/A R
70
SHUTDOWN
1 SOURCE
Input used for Shutdown 1
Source Value
0 UINT16 R/W
Ø (NONE) 0
TC1 1
TC2 2
TC BMS 3
XDCR 4
PS1 5
PS2 6
71
SHUTDOWN
1 LOGIC
Operating logic of Shutdown 1
Logic Value
UINT16 R
HIGH ON
LOW OFF
0
HIGH OFF
LOW ON
1
WINDOW 2
INV
WINDOW
3
72
SHUTDOWN
1 HIGH
LEVEL
Shutdown 1 upper limit
Range Value
1 INT16 R/WMin -32768
Max 32767
73
SHUTDOWN
1 LOW LEVEL
Shutdown 1 lower limit
Range Value
0 INT16 R/WMin -32768
Max 32767
74 - 79 UNUSED Unused N/A R
80
SHUTDOWN
2 SOURCE
Input used for Shutdown 2
Source Value
0 UINT16 R/W
Ø (NONE) 0
TC1 1
TC2 2
TC BMS 3
XDCR 4
PS1 5
PS2 6

Other manuals for Cimarron ARCONTROL BMS