63
Table 3.5.1 · MODBUS register map - conguraon registers (connued)
REGISTER
NUMBER
NAME DESCRIPTION
OPTIONS and
REGISTER VALUE
DEFAULT
DATA
TYPE
READ
or
WRITE
94 - 99 UNUSED Unused N/A R
100
PROCESS
1 VALVE
DEADTIME
Minimum amount of me in
seconds that the valve output
must be either acve or inacve
before it may toggle again
Range Value
5 UINT16 R/WMin 0
Max 10
101
PROCESS 1
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
102
PROCESS 2
VALVE DEAD
TIME
Minimum amount of me in
seconds that the valve output
must be either acve or inacve
before it may toggle again
Range Value
5 UINT16 R/WMin 0
Max 10
103
PROCESS
VALVE 2 PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
104
PROCESS 3
VALVE DEAD
TIME
Minimum amount of me in
seconds that the valve output
must be either acve or inacve
before it may toggle again
Range Value
5 UINT16 R/WMin 0
Max 10
105
PROCESS 3
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
106
PILOT VALVE
PWM DUTY
CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
107
BMS MODULE
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
108
INDEPENDENT
PROCESS
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
109
INDEPENDENT
PROCESS
VALVE PWM
DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 25
Max 100