63
Table 3.5.1 · MODBUS register map - conguraon registers (connued)
REGISTER
NUMBER
NAME DESCRIPTION
OPTIONS and
REGISTER VALUE
DEFAULT
DATA
TYPE
READ
or
WRITE
94 - 99 UNUSED Unused N/A R
100
PROCESS
1 VALVE
DEADTIME
Minimum amount of me in
seconds that the valve output
must be either acve or inacve
before it may toggle again
Range Value
5 UINT16 R/WMin 0
Max 10
101
PROCESS 1
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
102
PROCESS 2
VALVE DEAD
TIME
Minimum amount of me in
seconds that the valve output
must be either acve or inacve
before it may toggle again
Range Value
5 UINT16 R/WMin 0
Max 10
103
PROCESS
VALVE 2 PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
104
PROCESS 3
VALVE DEAD
TIME
Minimum amount of me in
seconds that the valve output
must be either acve or inacve
before it may toggle again
Range Value
5 UINT16 R/WMin 0
Max 10
105
PROCESS 3
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
106
PILOT VALVE
PWM DUTY
CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
107
BMS MODULE
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
108
INDEPENDENT
PROCESS
VALVE PWM
DUTY CYCLE
Duty cycle in % for the valve’s
PWM operaon
Range Value
25 UINT16 R/WMin 25
Max 100
109
INDEPENDENT
PROCESS
VALVE PWM
DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 25
Max 100

Other manuals for Cimarron ARCONTROL BMS