64
Table 3.5.1 · MODBUS register map - conguraon registers (connued)
REGISTER
NUMBER
NAME DESCRIPTION
OPTIONS and
REGISTER VALUE
DEFAULT
DATA
TYPE
READ
or
WRITE
110
PROCESS 1
VALVE PWM
DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 0
Max 1000
111
PILOT VALVE
PWM DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 0
Max 1000
112
PROCESS 2
PWM DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 0
Max 1000
113
PROCESS 3
PWM DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 0
Max 1000
114
BMS
MODULE
VALVE PWM
DELAY
Amount of me in milliseconds
that the output is fully on before
the valve output starts PWM
operaon
Range Value
100 UINT16 R/WMin 0
Max 1000
115 - 119 UNUSED Unused N/A R
120
BATTERY LVD
- OK LEVEL
Threshold for baery voltage, in
millivolts, that the baery voltage
must reach or go above before the
system can clear the LOW BATTERY
alarm state
Range Value
12500 UINT16 R/WMin 10000
Max 30000
121
BATTERY LVD
- LOW LEVEL
Threshold for baery voltage,
in millivolts, that if the baery
voltage reaches or goes below
cause the system to transion to
LOW BATTERY state
Range Value
11500 UINT16 R/WMin 10000
Max
25000
122 - 124 UNUSED Unused N/A R
125
MODBUS
ADDRESS
Modbus address of the ARControl
through the Modbus RS-485 port
Range Value
1 UINT16 R/WMin 1
Max 247