66
Table 3.5.1 · MODBUS register map - conguraon registers (connued)
REGISTER
NUMBER
NAME DESCRIPTION
OPTIONS and
REGISTER VALUE
DEFAULT
DATA
TYPE
READ
or
WRITE
137
TRANSDUCER
UNITS
The units
displayed in
the transducer
reading
Name Units Value
1 UINT16 R/W
Arbitrary Units a.u. 0
Ounce per inch
squared
oz/in
2
1
Pound per inch
squared
psi 2
Kilopascal kPa 3
Inches of water
in-H
2
O
4
Cenmeter of
water
cm-H
2
O
5
Kilogram per
cenmeter
squared
kg/cm
2
6
Degree
Fahrenheit
°F 7
Degree Celsius °C 8
Millivolt mV 9
Microamp µA 10
Percentage % 11
138
TRANSDUCER
DECIMAL
PLACE
Posion of the decimal place
displayed in the transducer
reading
Range Value
1 UINT16 R/WMin 0
Max 2
139 UNUSED Unused N/A R
140 OFFSET TC1
The amount of oset to be
applied to the thermocouple
measurement
Range Value
0 INT16 R/WMin -32768
Max 32767
141 OFFSET TC2
The amount of oset to be
applied to the thermocouple
measurement
Range Value
0 INT16 R/WMin -32768
Max 32767
142 TC UNITS
The units used for the
thermocouple measurement
Units Value
0 INT16 R/W°F 0
°C 1
143 - 144 UNUSED Unused 0 N/A R
145 ALARM MODE
Whether the ALARM output is
normally open or normally closed
when inacve.
Mode Value
1 UINT16 R/WN.C. 1
N.O. 0